Figure 1: Transmission of Transient Voltage through the Start-Finish Data Cable
All insights

Lightning Investigation

A Reverse Angle Photo Finish Camera (RAPFC), located at the finishing post of a horse racing track, was reported to have failed. The incident was discovered by…

2 min read

A Reverse Angle Photo Finish Camera (RAPFC), located at the finishing post of a horse racing track, was reported to have failed. The incident was discovered by the operator when he noticed that the computer at the Stipes and Judge room failed to establish a connection to the RAPFC at the Finishing Post.

He stated that there was a heavy thunderstorm prior to the discovery of the malfunction. Immediately, he informed the CCTV Engineer about the incident. The Engineer tried to rectify the problem by rebooting the RAPFC and computer, but the problem still persisted. He then informed the vendor about the incident and upon further inspection, it confirmed that the RAPFC was faulty and it was suspected that the damage was caused by a lightning strike. AGI’s Forensic Team detailed inspection of the Printed Circuit Boards (PCBs) of the RAPFC did not reveal any burn marks or bulges, which may indicate incidents of voltage surge(s). In order to test the functionality of the camera, a power supply was connected to the RAPFC. A laptop was then attached to the camera via an Ethernet cable. However, the RAPFC was unable to establish a connection with the laptop. The examination above shows that the RAPFC had malfunctioned. In the event of an indirect lightning strike, the transient voltage may be electromagnetically induced onto the underground start-finish cables. The transient voltage would then follow the path of least resistance to the RAPFC. As the electromagnetically induced voltage is weaker, there may or may not be burn marks evident on the affected devices.

Photograph 1: View of the grounding point of the Finishing Post. The grounding point is located about twenty-five (25) metres from the finishing post.
Photograph 2: View of the testing conducted on the RAPFC at the Finishing Post. A laptop was directly connected to the RAPFC through an Ethernet cable. The RAPFC failed to establish a connection with the laptop.
Agi forensic investigation lightning investigation photograph
Photograph 4: Interior view of the RAPFC. No burn marks or bulges were observed on the Printed Circuit Boards (PCBs).

Based on the evidence, the statements of witnesses and from the process of elimination of all possible causes, the RAPFC failed due to an indirect lightning strike.

  • The team recommends the installation of Surge Protector Devices (SPD) on the data cables to protect from transient voltage. It is essential not to place the protected cables next to the unprotected cables to avoid induced voltage onto the unprotected cables.

Keep reading

Related insights

All insights
  • The above picture shows initial stroke of signature A on exhibit E2 showing steep straight upstroke.

    Technical NoteForensic Investigation

    Signature Authorship Determination

    The forensic team of Approved Forensics Sdn Bhd (AFSB) was approached to determine the authorship of signatures on agreement documents.

    By AGI Team1 min read
    Read the technical note
  • Figure 1: General view of the extent of fire damage onto the roof of the Restaurant B (red arrow) and the newly erected cement wall on top of the pre-existing low-level wall after the fire (blue arrow).

    Case StudyForensic Investigation

    Fire Investigation to Restaurant

    Approved Forensics Sdn Bhd (AFSB)’s Team received an assignment to investigate the origin of a fire involving 2 adjoining restaurants. Besides the cause fire…

    By AGI Team2 min read
    Read the case study
  • Agi fire and explosion investigation stage bus fire investigation figure

    Case StudyForensic Investigation

    Stage Bus Fire Investigation

    A stage bus caught fire during its operations when the driver stopped by the roadside to alight the passengers.

    By AGI Team1 min read
    Read the case study

24/7 response

Does this affect a claim you are handling?

Send us the detail and we will tell you what a proper investigation would need to establish.