An air handling unit (hereinafter referred to as AHU) room is normally equipped with a gaseous fire suppression system which utilised INERGEN…
An air handling unit (hereinafter referred to as AHU) room is normally equipped with a gaseous fire suppression system which utilised INERGEN, which is a mixture of nitrogen, argon and carbon dioxide gases, stored gas cylinders.
The system is also composed of mainly smoke detectors, discharge nozzles and control panels. Displayed below, the basic arrangement of the gaseous fire suppression system.
An explosion was reported to have occurred within the premises of a publication company. The Assistant Manager, was in the office when he heard the explosion. He then proceeded to level 1 and found that the explosion had occurred within the AHU L1.02 room. The AHU room was mainly equipped with the AHU and the gaseous fire suppression system. There were eighteen (18) units of INERGEN gas cylinder of the gaseous fire suppression system.
The team found only one (1) INERGEN gas cylinder unit was damaged in the incident (refer to Photograph 1).
Tear damage was observed from the middle downward of the INERGEN gas cylinder’s body (refer to Photograph 8 of Appendix 1).
The torn body was found opened outward with irregular jagged pattern. The upper section of the torn body and the lower section of the torn body revealed shearing characteristic. The shearing indicates the area which had failed last due to the explosion.

Further examination on the internal surface of the failed INERGEN gas cylinder revealed pitting along the fractured surface (refer to Photograph 2).

No discolouration or heat damage was observed on the outer colour of the affected INERGEN gas cylinder. Cross section of the fractured surface revealed brittle characteristic on the surface towards the inner surface and sheared characteristic towards the outer surface (refer to Photograph 3).
These characteristics indicate that the failure originated from within the INERGEN gas cylinder.

Corrosion is the degradation of a material due to a reaction with its environment. There are several types of corrosion which include:
Pitting occurs when one (1) area of a metal surface become anodic with respect to the rest of the surface. There are several causes of pitting corrosion which include:
Stress-corrosion cracking (hereinafter referred as SCC) is a cracking phenomenon that occurs in susceptible alloy and is caused by the conjoint action of tensile stress and the presence of a specific corrosive environment. SCC occur under three (3) conditions:
Further examination on the pitting revealed the formation of crack transversing along the diameter of the pit (refer to Photograph 4).

ASM international state that under the ‘corrosion tunnel model’, tunnels of corrosion are formed at the crack tip until the ligaments fractured in a ductile manner. The crack thus propagated by alternating corrosion and ductile rupture.

The formation of the pitting corrosion on the inner surface of the INERGEN gas cylinder created a susceptible area for crack. Under the stress of the INERGEN gas pressure, the metal surface was constantly under stress which promoted the propagation of the crack.
The crack propagation continued to the extent that the gas cylinder could not further contained the pressure of the INERGEN gas thus causing the rupture of the INERGEN gas cylinder and causing the explosion.
Based on the damage analysis, witness accounts, the process of elimination, as well as physical evidence found on-site, the explosion was found to have originated from corrosion of the inner surface of the INERGEN gas cylinder.
Keep reading

ArticleForensic Investigation
The Vehicle Identification Number (hereinafter referred to as VIN) is the identifying code for a specific vehicle comprising of 17 alphanumeric characters…

ArticleForensic Investigation
The operator of a Tower Crane was using it to lift up an object from the floor ground to the operator’s cabin. He noticed that the boom had deformed at the…

ArticleForensic Investigation
Approved Group International’s (AGI) Senior Forensic Consultant Arthur Kong speaks at The Malaysian Insurance Institute is hosting a seminar titled “Railway…
24/7 response
Send us the detail and we will tell you what a proper investigation would need to establish.