Used widely across many industries, storage tanks are durable and long-lasting. However, many run the risk of damage if proper care is not practised.
Used widely across many industries, storage tanks are durable and long-lasting. However, many run the risk of damage if proper care is not practised. An imploded tank can cause your business valuable time and finances, so read on to discover one of the common causes of this equipment failure and what to look out for.
On 19 June 2019, a storage tank (R1) in a local facility imploded followed by a loud noise during an unloading operation to a road tanker. All operations were stopped immediately after the incident.
Imploded north-east section of R1
Slight bend on staircase structure
AGI was requested to conduct an onsite investigation to identify the cause of the storage tank implosion. The investigation included interviews conducted with relevant parties who were present during the incident as well as photos and sketches of observations seen onsite followed by a detailed analysis.
Below are the findings and results of the investigation and examination of the origin and cause of the storage tank implosion.
Upon establishing the chronology of incidents leading up to the storage tank implosion, it was identified that to fulfil the requirements to cater methanol storage, in January, the goose neck of R1 was to be replaced with a blank flange, while a breather valve was required to be connected on another spare flange. However, as a blank flange was unavailable, the goose neck was blanked by inserting a metal sheet between it and the connecting flange. A breather valve was then fixed on the connecting spare flange. Methanol was unloaded somewhere in the mid of March, following that the R1 was loaded with palm stearin.
In May, another storage tank required the breather valve, hence the breather valve from R1 with palm stearin in it was transferred to the other tank.. The following month during the unloading of the tank R1, the implosion occurred prompting a cease in operation.
Based on the damage assessment carried out by the team, several observations such as minor oxidation on the exterior valves, flanges and bolts, heavily corroded condensate pipeline, modified branch pipelines were noted.
Oxidation
Oxidation
Modified pipeline connected to the tank inlet
R1 inlet pipeline modified
R1 had imploded across its top and middle segments, however it did not suffer any significant damage. Paint coatings remained intact on the surface of dented areas inside the tank.
Imploded south-west section of R1
Imploded south-west section of R1
AGI identified four possible causes of the implosion, namely:
The cause of R1’s implosion was due to inadequate ventilation. As storage tanks undergo enormous amount of stresses due to pressure, temperature and volume changes, AGI recommends an addition of analogue pressure gauge to be introduced to them. This allows the tank pressure to be constantly observed during operation.
AGI uses investigational techniques to identify the proximate and root cause of failures such as this. Our findings are then compiled into a comprehensive report that will withstand scrutiny in a court of law. Need our assistance? Get in touch with us now!
Keep reading

ArticleForensic Investigation
The Suez Canal provides the shortest sea link between Asia and Europe, seeing to about 12% of global trade passing through it. Recently, a giant container ship…

Case StudyForensic Investigation
On the night of 22 August 2020, a Hotel’s Maintenance & Engineering (M&E) Manager was doing his patrolling rounds when he was informed of an incident involving…

ArticleForensic Investigation
Fire, broken down machines, electrical and motor vehicle failures can grind operations to a halt and cost businesses a lot of money.
24/7 response
Send us the detail and we will tell you what a proper investigation would need to establish.