Arson or incendiary fire is a crime of intentionally setting a fire to a property with the intent to cause damage. The motives often include financial gain, act of revenge and juvenile delinquency. However, like any other fire, incendiary fire can be identified and distinguished from other types of fire. One of the method is through the fire patterns that are formed when the products of combustion (smoke) come into contact with a surface. In a way, the fire tells the investigator how it behaves during the incident through various fire patterns. At approximately 2200 hours on 22 May 2017, John was having supper with a friend at a restaurant when he suddenly noticed black smoke emanating from the following block away from the restaurant. By-passers began to notice the smoke and stopped to have a look. The smoke was seen coming out from a closed shop lot. Moments later, John heard 2 explosions. He then immediately notified the Fire and Rescue Department. Upon the Team’s visit, the affected the two (2) shop lots designated as SL1 and SL2:

From the onsite inspection, the Team noted 3 areas with severe fire damage while the remaining area sustained high fire damage. 2 of the areas with severe fire damage were located in SL2 while another one area with severe fire damage was located in SL1.

Photograph 1: The rear section of SL1; elevated fire damage was seen in this area as the plastic components that were hang for decoration were melted (yellow arrows), frames and posters located on a higher level were ignited and dropped down (red arrows).
Photograph 1: The rear section of SL1; elevated fire damage was seen in this area as the plastic components that were hang for decoration were melted (yellow arrows), frames and posters located on a higher level were ignited and dropped down (red arrows).

A distinct V-pattern was seen at the rear roller shutter of SL1 which indicates that the fire was intense at the lower level. However, further examination revealed that the roller shutter casing was made of wood material. Hence, when the hot smoke accumulated at ceiling level, the high temperature ignited the wood material of the roller shutter casing and the dropped down debris ignited the combustible materials beneath.

Photograph 2: A distinct V-pattern (yellow dotted lines) was seen at the rear roller shutter of SL1 which indicates that the fire was intense at the lower section. Note the roller shutter casing at the end was partially charred (red arrow) while the metal frame located at the middle section was severely oxidized (yellow arrow).
Photograph 2: A distinct V-pattern (yellow dotted lines) was seen at the rear roller shutter of SL1 which indicates that the fire was intense at the lower section. Note the roller shutter casing at the end was partially charred (red arrow) while the metal frame located at the middle section was severely oxidized (yellow arrow).

Close examination of the severely damaged areas in SL2 revealed that there are residue of solidified polyurethane foam and ruptured polyurethane foam spray cans. According to the owner of the premises, the polyurethane foam spray cans are used for sound absorption where it is sprayed into empty cavities of the vehicle to reduce noise. Due to the presence of these polyurethane foam spray cans, the severe fire damage sustained in these areas was plausible. Nevertheless, there was no source of ignition in these two areas.

Photograph 3: One of the areas with severe fire damage showing residues of solidified polyurethane foam (red arrows) from the ruptured polyurethane foam spray cans (yellow arrow).
Photograph 3: One of the areas with severe fire damage showing residues of solidified polyurethane foam (red arrows) from the ruptured polyurethane foam spray cans (yellow arrow).

However, the severe fire damage in SL1 was questionable. The fire pattern in the severely damaged area of SL1 was suspicious as this area sustained low elevation fire damage which indicates that the fire was intense at the lower section. There was no source of ignition within the area as well, the closest source of ignition was the electrical reticulation routed on top. Hence, the Team excavated the area to identify the source of ignition in the area.

Photograph 4: One of the areas with severe fire damage; note the clean burn pattern at low elevation (red arrow) and the fallen debris as the tiers collapsed (yellow arrows).
Photograph 4: One of the areas with severe fire damage; note the clean burn pattern at low elevation (red arrow) and the fallen debris as the tiers collapsed (yellow arrows).

The Team collected fire debris samples from all three (3) locations and the result for the fire debris analysis was positive for gasoline. The areas of origin and spread of fire is illustrated in the following figure.

An incendiary fire is detectable; although in some circumstances, the fire appears to be accidental and/or natural. Fire pattern analysis is one of the many ways that help fire investigators to determine how the fire spread. On-site fire pattern analysis coupled with other observation and laboratory analysis help strengthen the conclusion achieved.